英文版出口品质 (2 zones fire alarm control panel)
1. 多线系统主机可以与其他多线烟感温感 手报 声光通用。
2. 出口英文版 品质可靠
3. 金属外壳 安全耐用
1.1 Product Features
The panels have the following key features:
2 conventional input zones.
1 notification appliance circuits (NAC) with built-in synchronization for ANSI 3.41and Gentex.
The panel comes with a 2 amp power supply.
Dedicated alarm and trouble relays.
1 RS485 can be able to connect the other panel.
Housed in a 205mm W x 258mm H x 81mm D metal enclosure.
Enclosure supports two 12V, 4Ah backup batteries.
The panel can be used independently or connect by RS485.
Electrical Specifications
Primary AC 120VAC 50/60 Hz Power supply rating
240VAC 50/60 Hz
Power supply rating 2 Amps 24VDC
Maximum Battery Charging Current 0.98 Amps 26VDC
Initiating Device Circuits 2 Zones Alarm Zone 2
Normal Initiating Operating Voltage 23VDC, Maximum 26VDC, regulated
Normal Quiescent Current (normal status) <50mA
Alarm Current (not include the others) <150 mA
Short Circuit Initiating Current (per zone) 35mA Maximum
Maximum Initiating Resistance (per zone) 10 ohms
Initiating End-of-Line Resistor 4K7 ohms, 1/2W 5%
Standby Detector Current (per zone) 4mA maximum
Maximum Detector Count (per zone) 30 detectors
Initiating Cabling Type 18AWG Twisted Shielded pair (14 – 18 AWG)
Detector Base Impedance 430 ohms
Notification Appliance Circuits 1 NACs, Special Application
Maximum NAC Current Rating 1 Amp maximum per circuit
NAC Operating Voltage 26VDC Nominal, 30VDC Maximum
NAC End-of-line Resistor 1N4007 Diode
FAULT Relay rating 2A & 30VAC, resistive
Alarm( Auxiliary ) Relay rating 2A & 30VAC, resistive
Master alarm panel Digital & LED display
Slave alarm panel LED display only