    Features

    • ETL LISTED Certified to CSA C22.2 No 61010-1, Conforms to UL Std. 61010-1, UL Std. 20751

    • Low-level meter capable of displaying from 0-200 ppm of CO

    • The CM-xx meets the Uniform Building Code for enclosed garages and meets OSHA standards for CO exposure

    • Selectable fan and alarm relay activation

    • 5 A SPDT fan relay controls starters of exhaust fans

    • 0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels

    • 4-20 mA Current Loop

    • CM-xx mounts on a standard 4x4 electrical box and becomes cover for the box

    • Supervised system: any internal detector problem will cause the fan & Alarm relay to activate

    • Calibration kit is available. One screw allows access for calibration or gas test

    Specifications

    • Shipping Weight: 1 pound (0.45 kg)

    • Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)

    • Color: White or Dark gray

    • Connections: plugs/terminals

    • Mounting box: (not included) 4x4 electric

    • Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching

    • Fan relay actuation: selectable at diS (disable), 15 ppm, 25 ppm, 35 ppm (default), 50 ppm or 100 ppm CO

    • Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes

    • Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes

    • Fan relay latching or not latching (default) selectable

    • Alarm relay: 0.5A 120 V, 60 VA

    • Alarm relay actuation: selectable N.O. (default) or N.C.

    • Alarm relay settings: diS, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default)

    • Current Loop, 4-20 mA for 0-200 ppm CO, selectable to ’bAS’ (default), ‘EnH’, OFF

    • Calibration Period Settings: dis(default), 3, 6, 12 and 24 (months)

    • Buzzer: 85 dBA at 10cm settable to off (default) or on

    • Digital display: 3-digit LED selectable to off (default) or on.

    • Operating Environment: 0°F to 125° F (-18oC to 52oC),10 to 90% RH non-condensing

    • Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC

    • Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA standby

    2.4.2 12-Series Line Voltage

    • Power: 100-240VAC (50 TO 60 HZ)

    • Current: 1.0 A MAX